Ürün Teknik Parametreleri
Standard:
| Standard | Description |
|---|
| ITU-TG.652 | Characteristics of a single mode optical fiber. |
| ITU-TG.655 | Characteristics of a non-zero dispersion -shifted single mode fibers optical. |
| EIA/TIA598 B | Col code of fiber optic cables. |
| IEC 60794-4-10 | Aerial optical cables along electrical power lines-family specification for OPGW. |
| IEC 60794-1-2 | Optical fiber cables -part test procedures. |
| IEEE1138-2009 | IEEE Standard for testing and performance for optical ground wire for use on electric utility power lines. |
| IEC 61232 | Aluminum -Clad steel wire for electrical purposes. |
| IEC60104 | Aluminum magnesium silicon alloy wire for overhead line conductors. |
| IEC 61089 | Round wire concentric lay overhead electrical stranded conductors. |
Colors -12 Chromatography:
| No. | 1 | 2 | 3 | 4 | 5 | 6 |
|---|
| Color | Blue | Orange | Green | Brown | Gray | White |
|---|
| No. | 7 | 8 | 9 | 10 | 11 | 12 |
|---|
| Color | Red | Black | Yellow | Violet | Pink | Aqua |
|---|
Technical Parameter:
Typical Design for Single Layer:
| Specification | Fiber Count | Diameter (mm) | Weight (kg/km) | RTS (KN) | Short Circuit (KA2s) |
|---|
| OPGW-32 (40.6;4.7) | 12 | 7.8 | 243 | 40.6 | 4.7 |
| OPGW-42 (54.0;8.4) | 24 | 9 | 313 | 54 | 8.4 |
| OPGW-42 (43.5;10.6) | 24 | 9 | 284 | 43.5 | 10.6 |
| OPGW-54 (55.9;17.5) | 36 | 10.2 | 394 | 67.8 | 13.9 |
| OPGW-61 (73.7;17.5) | 48 | 10.8 | 438 | 73.7 | 17.5 |
| OPGW-61 (55.1;24.5) | 48 | 10.8 | 358 | 55.1 | 24.5 |
| OPGW-68 (80.8;21.7) | 54 | 11.4 | 485 | 80.8 | 21.7 |
| OPGW-75 (54.5;41.7) | 60 | 12 | 459 | 63 | 36.3 |
| OPGW-76 (54.5;41.7) | 60 | 12 | 385 | 54.5 | 41.7 |
Typical Design for Double Layer:
| Specification | Fiber Count | Diameter (mm) | Weight (kg/km) | RTS (KN) | Short Circuit (KA2s) |
|---|
| OPGW-96 (121.7;42.2) | 12 | 13 | 671 | 121.7 | 42.2 |
| OPGW-127 (141.0;87.9) | 24 | 15 | 825 | 141 | 87.9 |
| OPGW-127 (77.8;128.0) | 24 | 15 | 547 | 77.8 | 128 |
| OPGW-145 (121.0;132.2) | 28 | 16 | 857 | 121 | 132.2 |
| OPGW-163 (138.2;183.6) | 36 | 17 | 910 | 138.2 | 186.3 |
| OPGW-163 (99.9;213.7) | 36 | 17 | 694 | 99.9 | 213.7 |
| OPGW-183 (109.7;268.7) | 48 | 18 | 775 | 109.7 | 268.7 |
| OPGW-183 (118.4;261.6) | 48 | 18 | 895 | 118.4 | 261.6 |
Ürün Açıklaması

Applications:
Ana Özellikler:
-
Küçük kablo çapı, hafif, kuleye düşük ek yük;
-
Çelik boru, kablonun ortasında, ikinci bir mekanik yorulma hasarı olmadan bulunur.
-
Yan basınca, burulmaya ve gerilmeye karşı düşük direnç (tek katman).
Açıklamalar:
Kablo tasarımı ve fiyat hesaplaması için detay gereksinimlerinin bize gönderilmesi gerekmektedir. Aşağıdaki gereksinimler şarttır:
-
A, Güç iletim hattı gerilim seviyesi
-
B, lif sayısı
-
C, Kablo yapısı çizimi ve çapı
-
D, Çekme dayanımı
-
F, Kısa devre kapasitesi
Tip testi
Uluslararası kabul görmüş bağımsız bir test kuruluşunda veya laboratuvarda gerçekleştirilen benzer ürünün üreticinin sertifikasını ibraz ederek tip testinden feragat edilebilir. Tip testi yapılması gerekiyorsa, alıcı ile üretici arasında bir anlaşmaya varılan ekstra tip test prosedürüne göre yapılacaktır.
Rutin test
Tüm üretim kablo uzunluklarındaki optik zayıflama katsayısı, IEC60793-1-C1C 'ye (Geri saçılma tekniği, OTDR) göre ölçülür. Standart tek modlu lifler 1310nm' de ve 1550nm 'de ölçülür. Sıfır olmayan dağılım kaydırmalı tek modlu (NZDS) lifler 1550nm' de ölçülür.
Fabrika testi
Fabrika kabul testi, müşteri veya temsilcisi huzurunda sipariş başına iki numune üzerinde gerçekleştirilir. Kalite özellikleri için gereksinimler, ilgili standartlar ve kabul edilen kalite planları ile belirlenir.

Packaging Requirements:
- 1:All cables shall be wound on treated wooden spools that are not returnable
- 2:Cable ends must be firmly secured to the spool and protected with waterproof shrink caps
- 3:Each spool must include: Protective plastic wrapping layer ,Reinforcing wooden slats for stability,Minimum 1m of free cable end for testing purposes, Standard spool length: 3000mm (±2% tolerance allowed)
Cable Identification:
The outer jacket must display:
- 1、Unique sequential numbering every 1m (±1% variance permitted)
- 2、 Additional repeating markings at 1m intervals showing: Product code and fiber count, Manufacturer identification, Production date (month/year),Total cable length
Standard Packaging Dimensions:
| Length | Container | Size (L×W×H) | Net Mass | Total Mass |
|---|
| 2 km | Wood spool | 90×75×90 cm | 156 kg | 220 kg |
| 3 km | Wood spool | 100×68×100 cm | 240 kg | 280 kg |
| 4 km | Wood spool | 109×75×109 cm | 300 kg | 368 kg |
| 5 km | Wood spool | 129×72×129 cm | 400 kg | 480 kg |
Technical Reference:
- 1、 Standard cable diameter: 10.0mm
- 2、Maximum span distance: 100m
- 3、Contact sales team for complete technical specifications
Spool Marking Standards:
Permanent markings (minimum 25-30mm height) must appear on both sides of each spool:
- 1、 Company name and trademark
- 2、Contained cable length
- 3、Cable specifications (type/fiber count)
- 4、Winding orientation
- 5、Weight measurements (gross/net)
Note: All wooden packaging materials must undergo proper fumigation treatment prior to use.
Case
Angola Güç Hattı Koridoru İletişimi Projesi Örnek Olay İncelemesi | Omurga + Dış Mekan Fiber Optik Kablo Portföy Desteği Olarak OPGW Temini
+
Türkiye: YRTFiber 'in Türkiye' deki Büyükşehir Fiber Ağı Modernizasyonu
+
Endonezya: Endonezya 'da YRTFiber' in Metropolitan Alan Ağı Yükseltmesi
+
Zambiya: yrtfiber tarafından Yüksek Performanslı Dış Mekan Fiber Optik Kablo Temini
+
YRFFIBER Toplam 13 üretim hattına, modern tozsuz atölyelere ve yüksek performanslı işleme ekipmanına sahibiz. Hammadde alımından bitmiş ürün işlemeye, ürün kalite testine, paketleme ve ihracata kadar çok çeşitli üretim hatlarına sahibiz. Aşağıda atölyenin gerçek fotoğraflarından bazıları yer almaktadır.

1. What is the OPGW-2 central stainless steel tube fiber cable used for?
OPGW-2 is designed for installation in high-voltage power transmission networks. It provides dual functionality: grounding protection and high-capacity fiber optic communication, making it ideal for utility and telecom applications.
2. What is the structure of this cable?
This cable uses a central stainless steel loose tube to house and protect the optical fibers. Surrounding layers typically include aluminum or aluminum-clad steel wires for mechanical strength and conductivity.
3. What fiber types and core counts are supported?
The OPGW-2 cable supports 12 to 144 fiber cores using G.652D or G.655C single-mode fibers, ensuring compatibility with modern communication systems and long-haul transmission.
4. What are the mechanical and environmental benefits of this design?
The stainless steel tube offers excellent crush resistance, corrosion protection, and thermal stability, while the outer layer provides electrical conductivity and grounding during lightning strikes.
5. What makes this cable suitable for aerial installation on power lines?
Its robust construction and dielectric protection allow for direct installation on overhead transmission towers, with no separate grounding wire needed. It resists EMI, lightning, and harsh weather conditions.